Non-pressure tube type hot water boiler

Non-pressure tube type hot water boiler SEH Series SEH-100/200/300/400/500/600/800/1000/1300/1600/2000/2500
A new, easy-to-use method of heating and hot water using a non-pressure tube type hot water boiler.
- Product Features
-
- The water pipe is operated at a low temperature of 95℃ or lower, rarely needs to be replaced, and is maintained in a degassed state, so there is no need to worry about corrosion caused by dissolved oxygen. Since scale does not attach to the heat exchanger, fuel costs are reduced through high efficiency, and the lifespan is semi-permanent.
- The hot water is indirectly heated in a copper pipe heat exchanger, providing clean, rust-free hot water.
- Heat exchangers for heating and hot water circulation can be installed in a single pipe body, allowing for a wide range of uses. Additionally, since each heat exchanger is independent, there is no mixing of water, and installation and construction are simple.
- Anyone can operate without a license or inspection.
- By attaching a circulation pump to exchange heated water, it generates hot water in a short period of time and maintains high efficiency.
- Fuel costs can be significantly reduced by attaching a condensing economizer (pressurized high performance) to the exhaust gas flue area. (Optional)
- When equipped with the artificial intelligence control device SE-Ai system, operation and maintenance become easier. (Optional)
- How it Works
- It is a structure in which the expansion tank is directly attached to the boiler body, and is operated under 95℃ in a non-pressurized state. Temperature control switch, overheating prevention switch, water level controller, and overflow line are installed as standard to ensure safety from accidents such as damage or explosion. It is easy to handle without a license or inspection.
Product standard specifications performance table
Item\Type | Unit | SEH-100 | SEH-200 | SEH-300 | SEH-400 | SEH-500 | SEH-600 | SEH-800 | SEH-1000 | SEH-1300 | SEH-1600 | SEH-2000 | SEH-2500 | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Tube heat output | MW | 0.12 | 0.23 | 0.35 | 0.47 | 0.58 | 0.7 | 0.93 | 1.16 | 1.51 | 1.86 | 2.33 | 2.91 | |
kcal/h | 100,000 | 200,000 | 300,000 | 400,000 | 500,000 | 600,000 | 800,000 | 1,000,000 | 1,300,000 | 1,600,000 | 2,000,000 | 2,500,000 | ||
Heat transfer area | ㎡ | 6.1 | 8.2 | 9.3 | 11.3 | 12.8 | 14.2 | 16 | 22 | 25 | 28 | 30 | 36 | |
Thermal efficiency | % | 90 | ||||||||||||
Control method | - | ON-OFF | HIGH-LOW-OFF | |||||||||||
Power used | V | 220V×1Ø | 220V×3Ø / 380V×3Ø×4W | |||||||||||
Total power consumption | kw | 0.4 | 0.4 | 1.0 | 1.5 | 1.5 | 2.0 | 2.6 | 4.1 | 6.0 | 8.0 | 12 | 15 | |
Product weight | kg | 760 | 820 | 880 | 1,520 | 1,600 | 1,840 | 2,200 | 2,600 | 3,100 | 3,600 | 4,000 | 4,300 | |
Fuel consumption | Diesel | kg/h | 10.7 | 21.5 | 32.3 | 43.1 | 53.9 | 64.7 | 86.2 | 107.8 | 140.2 | 172.5 | 215.7 | 269.6 |
City gas(13A) | N㎥/h | 11.2 | 22.4 | 33.6 | 44.8 | 56.1 | 67.3 | 89.7 | 112.2 | 145.9 | 179.5 | 224.7 | 280.5 | |
LPG(Propane) | N㎥/h | 4.9 | 9.9 | 14.8 | 19.8 | 24.8 | 29.7 | 39.7 | 49.6 | 64.5 | 79.4 | 99.2 | 124.1 | |
kg/h | 10 | 20 | 30 | 40.1 | 50.1 | 60.1 | 80.2 | 100.2 | 130.3 | 160.4 | 200.5 | 250.7 | ||
LPG(Butane) | N㎥/h | 3.9 | 7.8 | 11.7 | 15.6 | 19.5 | 23.4 | 31.2 | 39.1 | 50.8 | 62.5 | 78.2 | 97.8 | |
kg/h | 10.1 | 20.3 | 30.4 | 40.6 | 50.8 | 60.9 | 81.3 | 101.6 | 132.1 | 162.6 | 203.3 | 254.1 | ||
Connection diameter | Refueling port | A | 8 | 15 | 15 | 15 | 20 | 20 | 20 | 20 | 25 | 25 | 25 | 25 |
Gas inlet | A | 20 | 25 | 32 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | |
Drain | A | 25 | 32 | 40 | 40 | 50 | 50 | 50 | 50 | 65 | 65 | 65 | 80 | |
Flue | ømm | 200 | 200 | 250 | 250 | 300 | 300 | 350 | 400 | 400 | 450 | 500 | 500 | |
Appearance | Width (W) | mm | 1,050 | 1,140 | 1,160 | 1,280 | 1,280 | 1,290 | 1,420 | 1,580 | 1,650 | 1,820 | 2,100 | 2,300 |
Length (L) | mm | 1,880 | 2,130 | 2,320 | 2,660 | 2,960 | 2,960 | 3,360 | 3,380 | 3,460 | 3,650 | 3,940 | 4,250 | |
Height (H) | mm | 1,680 | 1,780 | 1,900 | 2,000 | 2,000 | 2,050 | 2,100 | 2,300 | 2,500 | 2,600 | 2,700 | 2,850 |
For heating and hot water circulation (60℃~70℃, 50℃~70℃ for SEV-1300 and above)
Item\Type | Unit | SEH-100 | SEH-200 | SEH-300 | SEH-400 | SEH-500 | SEH-600 | SEH-800 | SEH-1000 | SEH-1300 | SEH-1600 | SEH-2000 | SEH-2500 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Rated heat output | kcal/h | 100,000 | 200,000 | 300,000 | 400,000 | 500,000 | 600,000 | 800,000 | 1,000,000 | 1,300,000 | 1,600,000 | 2,000,000 | 2,500,000 |
Circulating amount | ㎥/h | 10 | 20 | 30 | 40 | 50 | 60 | 80 | 100 | 65 | 80 | 100 | 125 |
Max. operating water head pressure | mAq | 100 (10kg/㎠) | |||||||||||
Head pressure loss | mAq | 0.7 | 1.1 | 1.4 | 1.7 | 2.0 | 2.2 | 2.7 | 3.1 | 3.2 | 3.5 | 3.9 | 4.3 |
Heat exchanger | Material | Copper tube | |||||||||||
Heating inlet/outlet diameter | A | 40 | 50 | 65 | 80 | 80 | 100 | 100 | 125 | 125 | 125 | 150 | 150 |
for Hot water supply (5℃~65℃)
Item\Type | Unit | SEH-100 | SEH-200 | SEH-300 | SEH-400 | SEH-500 | SEH-600 | SEH-800 | SEH-1000 | SEH-1300 | SEH-1600 | SEH-2000 | SEH-2500 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Rated heat output | kcal/h | 100,000 | 200,000 | 300,000 | 400,000 | 500,000 | 600,000 | 800,000 | 1,000,000 | 1,300,000 | 1,600,000 | 2,000,000 | 2,500,000 |
Amount of hot water | ㎥/h | 1.7 | 3.3 | 5 | 6.5 | 8.3 | 10 | 13.3 | 16.7 | 21.7 | 26.7 | 33.3 | 41.6 |
Max. operating water head pressure | mAq | 100 (10kg/㎠) | |||||||||||
Head pressure loss | mAq | 0.5 | 0.8 | 1.1 | 1.1 | 1.2 | 1.4 | 1.5 | 1.7 | 2.5 | 3.3 | 3.6 | 4.0 |
Heat exchanger | Material | Copper tube | |||||||||||
Hot water inlet and outlet diameter | A | 20 | 25 | 32 | 32 | 40 | 40 | 50 | 65 | 65 | 80 | 80 | 100 |
for Hot water supply (25℃~65℃)
Item\Type | Unit | SEH-100 | SEH-200 | SEH-300 | SEH-400 | SEH-500 | SEH-600 | SEH-800 | SEH-1000 | SEH-1300 | SEH-1600 | SEH-2000 | SEH-2500 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Rated heat output | kcal/h | 100,000 | 200,000 | 300,000 | 400,000 | 500,000 | 600,000 | 800,000 | 1,000,000 | 1,300,000 | 1,600,000 | 2,000,000 | 2,500,000 |
Amount of hot water | ㎥/h | 2.5 | 5 | 7.5 | 10 | 12.5 | 15 | 20 | 25 | 32.5 | 40 | 50 | 62.5 |
Max. operating water head pressure | mAq | 100 (10kg/㎠) | |||||||||||
Head pressure loss | mAq | 0.7 | 0.8 | 1.2 | 1.3 | 1.5 | 1.7 | 1.8 | 2.0 | 2.3 | 2.6 | 3.0 | 3.5 |
Heat exchanger | Material | Copper tube | |||||||||||
Hot water inlet and outlet diameter | A | 20 | 32 | 32 | 40 | 50 | 50 | 65 | 65 | 80 | 100 | 100 | 125 |
The above specification performance table is based on the following :
- Steam pressure 0.7MPa[7kg/㎠], steam enthalpy 2.76MJ/kg[660.8kcal/kg], water temperature 293˚k(20˚C)
- Low calorific value of fuel
- Diesel : 43.12MJ/kg (10,300kcal/kg)
- Boiler kerosene : 43.4MJ/kg (10,368kcal/kg)
- City gas(13A) : 41.45MJ/Nm3 (9,900kcal/Nm3)
- This specification performance table may be changed without notice for quality improvement.